BARTEC - LINE Ex1 Series LED Exproof Linear Luminaire (ZONE 1 / 21)
Technical Specifications:
• Zone Classification: Zone 1 / 2 (Gases), Zone 21 / 22 (Dusts)
• Ex Protection (Gas): Ex II 2G Ex eb mb IIC T4 Gb
• Ex Protection (Dust): Ex II 2D Ex tb IIIC T85°C Db
• ATEX Certificate: FTZÚ 26 ATEX 0011X
• IECEx Certificate: IECEx FTZU 26.0016X
• Protection Class: IP66 / IP67 – IK10
• Ambient Temperature: -30 °C ... +55 °C (depending on model)
• Power Supply: 220-240 V AC 50/60 Hz / 220-240 V DC
• Power Range: 15.8 W - 94.4 W (2,419 - 12,206 lm)
• Luminous Efficacy: up to 158 lm/W
• Colour Temperature: 5000 K standard (3000 / 4000 / 6500 K on request), CRI above 80
• Lifetime: L80B50 over 110,000 hours, ta 50 °C
• Emergency Lighting: 3 h autonomy (180 min / 830 lm), EA, ED and AD versions
• Dimming: DALI2 versions (ND, ED, AD)
• Body: PC polycarbonate, grey RAL 7035
• Diffuser: UV-resistant polycarbonate
• Closing Clips: 2 pcs stainless steel AISI 304
• Cable Entry: 2 x Ex plastic gland M20x1.5 (7-13 mm) and 2 x Ex plastic plug M20
• Glow Wire Test: 850 °C
• Terminals: Screwless three-pole terminal block, max. 4.0 mm2, LOOP-IN / LOOP-OUT ready
• Lengths: 670 / 1,280 / 1,580 mm – 4.1 - 6.7 kg
Lengths: 3 sizes – 670 mm, 1,280 mm and 1,580 mm (4.1 – 6.7 kg)
Versions: N0 normal ON/OFF, ND DALI2 dimmable, EA emergency 3 h with autotest, AD DALI2 and emergency 3 h with autotest, ED DALI2 and emergency 3 h with DALI inverter; 1 h emergency versions (E1, A1, D1) are available in the ordering code
Emergency lighting: 3 h autonomy, 830 lm emergency output; battery autotest function
Dimming: DALI2 driver option
Power options: steps from 15.8 W to 94.4 W (2,419 - 12,206 lm)
Colour temperature: 5000 K standard; 3000 K, 4000 K and 6500 K on request
Wiring: one-phase terminal block at one end as standard; one-phase or three-phase terminal blocks at both ends optional, LOOP-IN / LOOP-OUT ready for through wiring
Mounting: direct ceiling and wall fixing with stainless steel clips; chain suspension (LIXACM201), 3 m cable suspension (LIXACM200), 45° wall bracket set (LIXACM600), adjustable bracket set (LIXACM602)
Pole brackets: Ø 42 / 50 / 60 mm (LIXACM342 / 350 / 360), AISI 304 standard, AISI 316 on request
Protective cages: LIXACCL06, LIXACCL12 and LIXACCL15
Other: UV resistance allows use in uncovered outdoor areas; 850 °C glow wire test
Typical Applications:
Ideal for process corridors and walkways in refineries, petrochemical and chemical plants, pharmaceutical and food production facilities, pump stations and pipeline buildings, warehouses, silos and packaging areas with combustible dust risk, as well as offshore platforms and port facilities.
Need this product for your project?Our engineers help you choose the right model and prepare a quotation.